This medium-voltage cable from Liban Cables (Nexans Lebanon) consists of three stranded copper conductors with XLPE insulation, a copper tape screen, galvanised steel wire armour, and a PVC oversheath. Designed for underground power distribution and direct burial.
Every manufactured length undergoes routine testing including DC resistance, high-voltage, and partial discharge at 1.73 Uo per IEC 60502-2. Test certificates are issued for all lengths supplied.
Conductor: stranded copper
Insulation: XLPE (cross-linked polyethylene)
Screen: copper tape screen (CTS)
Armour: galvanised steel wire armour (GSWA)
Oversheath: PVC
Standard: IEC 60502-2
DC conductor resistance at 20°C: per IEC 60228 and IEC 60502-2 para. 16.1 & 16.2
High-voltage test: IEC 60502-2 para. 16.1 & 16.4
Partial discharge test: max. at 1.73 Uo per IEC 60502-2 para. 16.1 & 16.3